Operation and Maintenance Manual OM 751-4
Group: Unit Ventilator
Document PN: 106506346
Date: July 2014
MicroTech
®
II Controls for Daikin Classroom Unit
Ventilators
DX Cooling Only
Software Model UV05
Used with Daikin Classroom Unit Ventilator
Model AVV - Floor-Mounted
Model AHV - Ceiling-Mounted
Model AZU - Floor-Mounted Self-Contained Air Conditioner
IMPORTANT
Before unit commissioning, please read this publication in its entirety. Develop a thorough understanding before starting the
commissioning procedure.
This manual is to be used by the commissioner as a guide. Each installation is unique, only general topics are covered. The order in
which topics are covered may not be those required for the actual commissioning.
People and ideas you can trust.
Seitenansicht 0
1 2 3 4 5 6 ... 47 48

Inhaltsverzeichnis

Seite 1 - Ventilators

Operation and Maintenance Manual OM 751-4Group: Unit VentilatorDocument PN: 106506346Date: July 2014MicroTech® II Controls for Daikin Classroom Unit

Seite 2

OM 751-4 10 www.DaikinApplied.comGettInG started Using the Keypad/Display Viewing Actual Indoor Air Temperature (IAT) Normally, the effective set poi

Seite 3 - Contents

www.DaikinApplied.com 11 OM 751-4GettInG started Figure 5: Changing a keypad/display menu itemTable 7: Keypad/display menu item list DisplayKeypad me

Seite 4 - IntroduCtIon

OM 751-4 12 www.DaikinApplied.comDisplayKeypad menu item listAbr. DescriptionRO RW105 Defaultx5Exhaust Interlock OAD Min Position set pointEOADAdjus

Seite 5

www.DaikinApplied.com 13 OM 751-4Description of Operation State Programming The MicroTech II UVC takes advantage of “state” machine programming to de

Seite 6 - Acronyms/Abbreviations

OM 751-4 14 www.DaikinApplied.comdesCrIptIon of operatIon Figure 6: Complete UVC—state diagramLUI InputNetwork InputAUTOModeOFFMode(State 9)NIGHT PU

Seite 7

www.DaikinApplied.com 15 OM 751-4desCrIptIon of operatIon Table 8: UVC state names and numbersNormal UVC modes State namesState numbersDecimal ASCII

Seite 8 - Keypad Functions

OM 751-4 16 www.DaikinApplied.comdesCrIptIon of operatIon Night Purge Mode (State 8) Night Purge mode is provided as a means to more easily and quic

Seite 9

www.DaikinApplied.com 17 OM 751-4desCrIptIon of operatIon Emergency Heat Mode (Super State) The Emergency Heat mode is provided for situations where

Seite 10 -   

OM 751-4 18 www.DaikinApplied.comdesCrIptIon of operatIon Cool Mode (Super State) When in Cool mode the UVC uses primary cooling (economizer) and se

Seite 11 - GettInG started

www.DaikinApplied.com 19 OM 751-4desCrIptIon of operatIon The UVC monitors the DAT to ensure it does not fall below VCLL. The CO2 demand controlled

Seite 13 - Description of Operation

OM 751-4 20 www.DaikinApplied.comdesCrIptIon of operatIon Mech State (State 2) The Mech state is a “normal” state during Cool mode. The Mech state t

Seite 14 - UVC Unit Modes

www.DaikinApplied.com 21 OM 751-4desCrIptIon of operatIon Special Purpose Unit ModesThere are some additional UVC modes that are considered special

Seite 15 - WARNING

OM 751-4 22 www.DaikinApplied.comdesCrIptIon of operatIon Unit Mode Priority The UVC uses the network variables and binary inputs listed in Table 10

Seite 16 - Fan Only Mode (State 10)

www.DaikinApplied.com 23 OM 751-4desCrIptIon of operatIon Occupancy Modes The UVC is provided with four occupancy modes: Occupied, Standby, Unoccupi

Seite 17 - Auto Mode

OM 751-4 24 www.DaikinApplied.comdesCrIptIon of operatIon Additional Occupancy Features Networked Occupancy Sensor Capability A networked occupancy

Seite 18 - Cool Mode (Super State)

www.DaikinApplied.com 25 OM 751-4desCrIptIon of operatIon Space Temperature Set Points The UVC uses the six occupancy-based temperature set points a

Seite 19

OM 751-4 26 www.DaikinApplied.comdesCrIptIon of operatIon Remote Wall-Mounted Sensor with 55°F to 85°F Adjustment (optional) When the optional remot

Seite 20

www.DaikinApplied.com 27 OM 751-4desCrIptIon of operatIon Table 15: Setpoint calculation examplesExample A – Stand-Alone Unit, No remote sensor, No

Seite 21 - Special Purpose Unit Modes

OM 751-4 28 www.DaikinApplied.comdesCrIptIon of operatIon Proportional Integral (PI) Control Loops The MicroTech II UVC uses PI-loop control for hea

Seite 22 - Unit Mode Priority

www.DaikinApplied.com 29 OM 751-4desCrIptIon of operatIon PI Control Parameters Associated with each PI loop is a set of two adjustable parameters:

Seite 23 - Occupancy Modes

www.DaikinApplied.com 3 OM 751-4ContentsIntroduction ...4Acronyms/Abbreviatio

Seite 24 - Unit-Mounted Time-Clock

OM 751-4 30 www.DaikinApplied.comdesCrIptIon of operatIon Integral Time The integral time, or integral action, causes the controlled output to chang

Seite 25 - Space Temperature Set Points

www.DaikinApplied.com 31 OM 751-4desCrIptIon of operatIon Indoor Air Fan interlock with Compressor OperationThe IA fan will turn on with compressor

Seite 26 - (optional)

OM 751-4 32 www.DaikinApplied.comdesCrIptIon of operatIon Temperature Comparison with OA Enthalpy Setpoint Economizer (optional) If the optional Exp

Seite 27

www.DaikinApplied.com 33 OM 751-4desCrIptIon of operatIon Networked Space Humidity Sensor Capability A networked space humidity sensor can be networ

Seite 28

OM 751-4 34 www.DaikinApplied.comdesCrIptIon of operatIon Compressor Operation The UVC is congured to operate the compressor as secondary (mechanic

Seite 29 - CAUTION

www.DaikinApplied.com 35 OM 751-4desCrIptIon of operatIon Floating-Point Actuator Auto-Zero, Overdrive and Sync For self-contained units, the UVC at

Seite 30 - Figure 20: Integral time

OM 751-4 36 www.DaikinApplied.comdesCrIptIon of operatIon External Binary Input 3 This input can be congured as a ventilation lockout (default) or

Seite 31 - Outdoor Air Damper Operation

www.DaikinApplied.com 37 OM 751-4desCrIptIon of operatIon External Binary Output 3 This output can only be used to signal exhaust fan operation (def

Seite 32

OM 751-4 38 www.DaikinApplied.comuVC Input and output table All UVC input and output connections and their corresponding unit ventilator usage are sh

Seite 33

www.DaikinApplied.com 39 OM 751-4dIaGnostICs and serVICe The most important aspect of troubleshooting unit ventilator controls is to isolate the sour

Seite 34 - Compressor Operation

OM 751-4 4 www.DaikinApplied.comIntroduCtIonThis manual provides information on the MicroTechI® II control system used in the Dai-kin Applied Unit V

Seite 35 - External Binary Inputs

OM 751-4 40 www.DaikinApplied.comdIaGnostICs and serVICe Space Temp Sensor Failure (f0) The Space Temp Sensor Failure fault occurs when the UVC detec

Seite 36 - External Binary Outputs

www.DaikinApplied.com 41 OM 751-4dIaGnostICs and serVICe Space Coil DX Temp Sensor Failure (f5) The Space Coil DX Temp Sensor Failure fault occurs wh

Seite 37 - External Binary Output 3

OM 751-4 42 www.DaikinApplied.comdIaGnostICs and serVICe Space CO2 Sensor Failure (optional) (fc) The Space CO2 Sensor Failure fault occurs when the

Seite 38

www.DaikinApplied.com 43 OM 751-4troubleshootInG temperature sensors The UVC is congured to use passive positive temperature coefcient (PTC) sensor

Seite 39 - Alarm and Fault Monitoring

OM 751-4 44 www.DaikinApplied.comdIaGnostICs and serVICe Troubleshooting Humidity Sensors The UVC is congured to use a 0–100% RH, 0–5 VDC, capacitiv

Seite 40 - DX Pressure Fault (f1)

www.DaikinApplied.com 45 OM 751-4dIaGnostICs and serVICe Troubleshooting Carbon Dioxide (CO2) Sensors The UVC is congured to use a 0–2000 PPM, 0–10

Seite 41 - IaGnostICs and serVICe

OM 751-4 46 www.DaikinApplied.comdIaGnostICs and serVICe UVC Conguration ParametersThe UVC is been provided with a number of conguration variables

Seite 42

www.DaikinApplied.com 47 OM 751-4Conguration parameter name Abr. Notes DefaultMenu item1Primary Cool Proportional Band 18°F (10°C)Primary Cool Integ

Seite 43

OM 751-4 ©2014 Daikin Applied (7/14) | (800) 432–1342 | www.DaikinApplied.comDaikin Applied Training and DevelopmentNow that you have made an

Seite 44

www.DaikinApplied.com 5 OM 751-4IntroduCtIonTable 4: Software program literature Description Manual # Air Source Heat Pump with Electric Heat (Softw

Seite 45 - ) Sensors

OM 751-4 6 www.DaikinApplied.comIntroduCtIonAcronyms/Abbreviations The following table list acronyms and abbreviations that may or may not be used w

Seite 46 - UVC Conguration Parameters

www.DaikinApplied.com 7 OM 751-4Description Acronym/Abr.National Electric Code NECOutside Air OAOutdoor Air Coil Temperature OACTOutside Air Dampers

Seite 47 - -4°F (-2.22°C)

OM 751-4 8 www.DaikinApplied.comGettInG started The MicroTech II Unit Vent Controller (UVC) is a self-contained device that is capable of complete,

Seite 48

www.DaikinApplied.com 9 OM 751-4GettInG started Table 6: Keypad/display security levels Level Display What is restricted? Password0uoDefault level (